Master Indsutrial

Technical sheet : Master Industrial


INDUSTRIAL ENVIRONMENT
Master Industrial is suitable for the most demanding installation environments where there are vibrations, mechanical stress, dust and, in general, where the operating conditions are unfavorable to products created for the standard UPS market.
HIGH ICC
The high short-circuit current (ICC = 3xIn) makes it suitable for loads which require high current peaks when switching on or during normal operation.
VOLTAGE DC 220 V
The input and inverter transformers ensure the isolation of the batteries, which are sized for a voltage of 220 VDC (108 to 114 cells), the standard industrial value.
REDUNDANT VENTILATION
Redundant 100% load ventilation is standard, which ensures normal load operation with half the fans running; in addition, each fan is monitored and an alarm signal is issued in the event of a failure. The characteristics of Easy Source input, Battery Care System, flexibility and communication capabilities are the same as those of the classic Master MPS range.